124 GE MDS entraNET Reference Manual 05-4055A01, Rev. D
Invisible place holder
Figure 5-4. Point-to-Point Serial-to-Serial Application Diagram
Use the Serial Configuration Wizard (Local Serial Configuration menu)
to make the settings listed in the table below. Following the table are
step-by-step screen images of the Wizard.
5.4.1 Step-by-step Instructions for Configuring a
Point-to-Point Serial Connection
1. Connect a powered AP radio to a PC.
2. At the PC, open a connection with the Access Point radio using a
terminal, Telnet, or Web browser session.
3. Press
G to display the Main Menu.
EIA-232
Terminal
or Computer
192.168.0.10
RTU
EIA-232
192.168.0.1
C
O
M
2
P
W
R
L
I
N
K
C
O
M
1
RemoteAccess Point
LAN
C
OM1
COM2
PWR
LINK
Table 5-4. Point-to-Point Serial-to-Serial Configuration
GE MDS entraNET
radio Location
Menu Item Setting
AP (COM2) Port Status Enabled
Mode Serial-to-Serial
Remote UnitID 1155999 (example)
Rem. COM Port COM2
Baud Rate 19200
Byte Format 8N1
Buffer Size 256 Bytes
Inter-Packet Delay 4
Remote radio (COM2) Mode Data
Baud 19200
Format 8N1
Buffer 256
DelayChars 4