MDS 05-4055A01, Rev. A MDS entraNET 900 System Guide 47
Inter-Packet Delay— Number of characters that rep-
resent the end of a message (inter-character time-out). A
transceiver receiving data through the serial port will send an
end-of-message signal to the remote end. MODBUS defines
a “3.5-character” parameter. [0–1,000; 0]
3.5.3 Remote Serial Gateway Configuration
(IP-to-Remote Serial)
The serial gateway controls the behavior of all Remote radios from the
perspective of IP encapsulation. The gateway is basically a table with
one entry for each Serial Remote radio. Ethernet radios are not defined
in the serial gateway. No further configuration is required at the Remote
radios.
The AP can be configured to accept IP traffic to be exchanged with
devices connected to the serial ports of one or more Remotes.
Figure 3-19 shows the starting point for configuring the Remote Serial
Gateway settings.
Invisible place holder
Figure 3-19. Serial Configuration for Remote Radios
RSG Talkback Enable (UDP IP-to-Serial)—When this
option is enabled, and the RSG is set up for UDP mode, a
message from a Remote radio (usually a reply to a poll) will
be sent to the last IP address/port that a message was received
from.
RSG Talkback Timeout—After this timeout has
expired (time since the last data has been received from an IP